- Project Location:
- Nashville, TN
- Status:
- Completed
- Structure Type:
- Government
Scope Of Work
Install utility monitoring devices to all listed buildings. Provide and install electric meters. Tie meters into DDC controls. Write software to integrate meters into DDC system. Meters need to monitor and send the following data: KW, KWH, Volts all phases, Amps all phases, PF. Data needs to be stored at the local level if communication to central is interrupted for 45 days. Data at the central head end needs to be programmed to be able to record each piece of data hourly, daily, monthly, yearly, at intervals of 15 minutes. Installation to meet ANG ETL 01-1-1 requirements. Installation to meet NEC requirements. Meter is to be Digital/solid state. Accuracy 0.5%. Readout should include Total Harmonic Distortion. Local read out at the meter.